Click on the Literature Downloads Button to access all the available literature for this product.

     

Ranco O and G series pressure controls are designed to switch electrical loads such as contactors, relays, fans and motors in HVAC and Commercial applications in response to changes in sensed refrigerant pressure.


APPLICATIONS

  • Control of suction pressure in either an operating or limit control role.
  • Control of high side pressure in either an operating or limit control role.
  • Condenser fan cycling.
  • Compressor Lube Oil Protection.

010 / 011 / 016 / 020
  • Heavy duty controller with NEMA 1 enclosure provides variety of mounting location options.
  • Laser welded stainless steel bellows for extended life and accurate, precise settings.
  • Super Cap® capillary protection system provides ten times more protection from vibration-induced breakage than controls with traditional capillary designs.
  • Setpoints are adjustable within several available ranges with fixed and adjustable differentials.
G20 / G23
  • Medium-duty rated pressure switch for mounting in an electrical panel.
  • Bellows-operated control with fixed setpoints.
  • Low (G20) and high (G23) pressure versions; automatic or manual reset (factory set).
012
  • Same features as above except low pressure suction and high pressure discharge functions are combined in one control.
  • High pressure reset can be "field converted" between manual and automatic.
070 / 071
  • Compact size and lightweight control for fixed setting pressure sensing.
  • Hermetically welded/brazed stainless steel snap discs/pressure fittings for long term leak protection.
  • Available in close on pressure rise (O70) and open on pressure rise (O71) versions.
  • SPST switch is watertight and environmentally sealed with epoxy resin.
  • Wire leads or quick-connect terminal electrical connections.


SPECIFICATIONS

Reset Switch Control Type Operating Range and Differential
(See table)
Connection Style
(See table)
Typical UL / CSA Ratings1
VAC (60 Hz) FLA LRA NIA PD, VA
Auto SPST O10 A,B,C,D,E 1,2,3 24
120
240

24
24

144
144
 
 
 
144
720
720
O11 A,B,F
O12 Low (A)
High (G or H)
Manual Low (J)
High (H)
Auto SPDT O16 A,B,C,D,E,N 120
240
2402
17
17
20
102
102
80
24
24
720
720
Manual F
Auto DPST O20 A,B,C,D,E 120
240

24
24

144
144
24
24
125
125
Auto / Manual SPST or
SPDT
G20 K 1,2 120 / 2403
120 / 2084
240
277
20
20
8.3
7
78
78
39
42
 
 
 
 
 
 
 
 
G23 L
Auto SPST O70 L,M 3,4,5 24
120 - 277
120
240


10
5


40
20
 
 
 
 
48
375
 
 
O71


TYPICAL DRAWINGS

G20

Click on the part number above to view the drawing.


OPERATING RANGE AND
DIFFERENTIAL TABLE

  Operating Range Differential
A 12" Hg to 50 PSI 5 to 35 PSI
B 10" Hg to 100 PSI 10 to 40 PSI
C 50 to 150 PSI 10 to 40 PSI
D 100 to 250 PSI 20 to 100 PSI
E 100 to 400 PSI 40 to 150 PSI
F 150 to 450 PSI 40 to 150 PSI
G 100 to 250 PSI 50 PSI Fixed
H 150 to 450 PSI 70 PSI Fixed
J 10" Hg to 100 PSI Fixed
K 5" Hg to 100 PSI Fixed Fixed
L 100 to 450 PSI Fixed Fixed
M 5 to 100 PSI Fixed Fixed
N 12" Hg to 80 PSI 5 to 38 PSI

CONNECTION STYLE

1. Capillary with 1/4" sweat tube (depth stop, optional)
2. Capillary with female flare nut (core depressor, optional)
3. Male flare
4. Female flare nut (core depressor, optional)
5. 1/4" sweat tube (depth stop, optional)

1 O10 / O11 / O12 / O16 / O20 are UL Listed Devices (UL File SA 512) and CSA Recognized under LR 32079. G20 / G23 / O70 / O71 are recognized under UL SA512 and CSA LR 1942. Confirm ratings with factory as they vary within control type.

2 Hermetic units only.

3 Three-wire power supply, 120 V ac to ground.

4 Four-wire power supply, 120 V ac to ground.

 

Go to top

© Copyright 1999-2007 Invensys Controls. All rights reserved.
Privacy PolicyLegal Information