Ranco Humidity controls are designed to regulate the relative humidity of confined spaces by cycling humidifying or dehumidifying equipment. They are designed for use as internal components for portable humidifiers and dehumidifiers, and as wall mounted humidity controls for central systems.


APPLICATIONS

  • Dehumidifiers.
  • Space and Product Humidifiers.
  • Ventilation fans for confined spaces.
  • Materials processing.
  • Central HVAC units

 

FEATURES

 
  • Strong plastic frame with integral switch.
  • Improved woven nylon sensing element provides 12 times faster speed of response than film nylon elements.
  • Greater stability of setpoints over dramatic changes in relative humidity.
  • Improved differential allowing 5%RH.
  • Switch grade plastic frame eliminates the need for grounding the control.
  • Choice of 5% or 15%RH differentials.
  • Choice of (2) SPST and (2) SPDT switches to better match applications.
  • Choice of fixed or adjustable setpoints.
  • Choice of dial shaft flat orientation.
  • Gold-plated contacts available for microprocessor load applications.
  • Available with case and cover for wall/duct mounting.
  • Electronic controls available contact Ranco Marketing.

SPECIFICATIONS

 
Humidity Ranges
10 to 60%RH.
20 to 80%RH.
30 to 90%RH.

 Differentials
 5%RH or 15%RH.

Switch

SPDT or SPST.
6.3 X 0.8 mm Terminals.

Function of Terminals (when present)
1 Close on %RH increase
2 Common.
3 Close on %RH decrease.

Switch/Frame Insulation Material
Thermoplastic, Flame Class 94V-0.
Comparative Tracking Index 600.

Approvals
The controls meet IEC 60730 - 1 & 2 - 13, UL 873 and CSA C22.2, No. 24.

Control Cycle Ratings
Automatic switch cycles @60° C 50000.
Manual dial shaft cycles 6000.

Ambient Temperature Limitations
Switch Head 0° C to 60° C.
Shipping -30° C to 65.6° C.

Enclosure Protection
IP00.

Electrical Shock Protection
Class 1.

Method of Attachment
Screw; Optional user defined snap-in.


TYPICAL SPECIFICATIONS

(No case/cover) Approved ratings at 125/250 VAC
Code Series Typical Application Switch Terminal Numbers Inductive, FLA, amps Inductive, LRA, amps Resistive, NIA, amps
J10 - 1000 Dehumidification SPST 2 - 1 12.0/3.7 50/22.2 12.0/3.7
J10 - 2000 Humidification SPST 2 - 3 12.0/3.7 50/22.2 12.0/3.7
J10 - 7000 &
J10 - 7300
Dehumidification & Humidification SPDT 2 - 1
2 - 3
12.0/3.7
2.0/1.0
50/22.2
12.0/6.0
12.0/3.7
2.0/1.0
J10 - 7100 Humidification & Dehumidification SPDT
SPDT
2 - 3
2 - 1
12.0/3.7
2.0/1.0
50/22.2
12.0/6.0
12.0/3.7
2.0/1.0
UL/CSA approved to 6000 cycles.
EN approved ratings are at 250 VAC only, 50000 cycles.
(With case/cover) UL/CSA Ratings Special Features
Code Series Function RH Range Switch VAC FLA LRA PD,VA
J10 - 808 Humidistat 10% - 60%
SPST <30 N/A N/A N/A Wall / Duct Mount (Not Shown)
J10 - 809 W
J10 - 809 V
Dehumidistat 20% - 80%
SPST <30 N/A N/A N/A Wall Mount
J10 - 810* Dehumidistat 20% - 80%
SPST 125 7.5 4.5 250 Wall Mount
(Verticle)
J10 - 821* Humidistat 20% - 80%
SPST 125
250
24
7.5
3.3
4.5
20
250
250
72
Wall Mount
(Horizontal)
*Ratings are CSA, NRTL only File LR 18321.
Note: J10 - 809 W = White Cover, J10 - 809 V =Verticle Mount.