ENVIRONMENTAL
Operating Temperature
Range -40°F to +140°F
Operating Humidity 0-95% non-condensing
Models in NEMA 1 enclosure should be mounted indoors in an
environment that is free of excessive contaminants such as
oil, moisture and dirt. Models in NEMA 3R non-metallic
enclosure are suitable for both indoor and outdoor use.
PHYSICAL
EC4000, EC4004
Enclosure NEMA 1 drawn steel enclosure with lockable
hasp. Weight Approximately 2 lbs. (0.9 kg)
Dimensions
Width 4-1/4” (10.8 cm)
Height 7-7/8” (20.0 cm)
Depth 3” (7.6 cm)
Display Size 1-3/4” x 11/16” (7 cm x 1.9 cm)
EC4000PC, EC4004PC & EC4005PC
Enclosure NEMA 3R Non-Metallic with Clear-View cover
Weight Approximately 2-1/2 lbs. (1.1 kg)
Dimensions
Width 6-9/16” (16.7 cm)
Height 8-1/8” (23.1 cm)
Depth 3-7/8” (9.8 cm)
Display Size 1-3/4” x 11/16” (7 cm x 1.9 cm)
HOW
TO SPECIFY
Installer shall
furnish and install Paragon EC4000, EC4004 or EC4005
Electronic Time Control. The single-channel control shall
have 24-hour capability with 16 events available. Control
shall have keyboard override until overridden again or until
next event is reached. Control shall provide 7 days power
outage carry-over without a battery. The digital time
display shall be 11/16” in height. Clock format shall be
selectable, allowing a choice of 12 hour (AM/PM) or 24 hour
format. An “ON” or “OFF” display will indicate the
current status of the load control contacts. Wiring
terminals shall have the capability to accommodate #16 to
#10 AWG wire. Control shall be housed in a NEMA 1, lockable
steel enclosure or a NEMA 3R lockable enclosure (with
Clear-View cover) to guard against vandalism or tampering.
|
ELECTRICAL
SPECIFICATIONS
| Model
No. |
Contact
Configuration |
Voltage |
|
| EC4000/120V |
SPDT |
120 Vac |
| EC4000PC/120V-RT* |
SPDT |
120 Vac |
| EC4000PC/120V* |
SPDT |
120 Vac |
| EC4000/208-277V |
SPDT |
208-277 Vac |
| EC4000PC/208-277V* |
SPDT |
208-277 Vac |
| EC4004/120V |
SPST |
120 Vac |
| EC4004PC/120V* |
SPST |
120 Vac |
| EC4004PC/120V-RT* |
SPST |
120 Vac |
| EC4004/208-277V |
SPST |
208-277 Vac |
| EC4004PC/208-277V* |
SPST |
208-277 Vac |
| EC4004PC/208-277V-RT* |
SPST |
208-277 Vac |
| EC4005PC/120,
208-277V-RT* |
DPST |
120/208-240
Vac |
*Supplied in a NEMA
3R non-metallic enclosure. PC suffix designates a
non-metallic enclosure with Clear-View cover. RT designates
retail packaging.
Frequency 50/60
Hz
Power Consumption 4 VA Max.
Wiring Terminals Accommodate #16 to #10 AWG wire
UL Listed, CSA Certified, and comply with FCC rules.
Power Outage Carry-Over
The program and time-of-day are maintained during a power
outage for a minimum of 7 days. A built-in, special
capacitor eliminates the inconvenience of battery
replacement.
Output Switch Ratings
Model
EC4000
Normally open contacts:
20 amp resistive (10 amp CSA) at 24-240 Vac
1 Hp (1/2 Hp CSA) at 120 Vac, 2 Hp (1 Hp CSA) at 240
Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac |
Model
EC4004
Normally open contacts:
30 amp resistive at 24-240 Vac (UL)
30 amp resistive at 120 Vac (CSA)
10 amp resistive at 240 Vac (CSA)
1 Hp at 120 Vac, 2 Hp at 240 Vac
5 amp tungsten at 120-240 Vac
6 amp ballast at 120-277 Vac |
Normally
closed contacts:
10 amp resistive at 24-240 Vac
1/4 Hp at 120 Vac, 1/2 Hp at 240 Vac
3 amp tungsten at 120-240 Vac
3 amp ballast at 120-277 Vac |
Model
EC4005PC
Normally open contacts:
30 amp resistive at 120-277 Vac
1 Hp at 120 Vac, 3 Hp at 240 Vac
15 amp tungsten at 120-277 Vac (UL)
5 amp tungsten at 240 Vac (CSA)
20 amp ballast at 120 Vac, 10 amp at 277 Vac |
|